Vibrator: EATON Model: LZMN3-A400-I Product type: Automatic generator Number of poles: 3 Nominal flow (In): 400 A Nominal operating voltage (Ue): 400/415 V AC Nominal insulation voltage (Ui): 690 V AC Nominal impulse withstand voltage (Uimp): 8 kV Nominal limit switching capacity (Icu) at 230 V AC: 70 kA Nominal operating switch building capacity (Ics) at 230 V AC: 70 kA Nominal limit switching capacity (Icu) at 400/415 V AC: 50 kA Nominal operating switching capacity (Ics) at 400/415 V AC: 50 kA Rated limit switching capacity (Icu) at 500 V AC: 36 kA Rated operating switch capacity (Ics) at 500 V AC: 36 kA Rated limit switching capacity (Ics) at 500 V AC building number (Icu) at 690 V AC: 6 kA Nominal operating switching capacity (Ics) at 690 V AC: 6 kA Frequency: 50/60 Hz Type of release agent: Thermomagnetic, fixed Adjustment of thermal release agent (Ir): 400 And in the form of re-imagination and short freezing Mechanical wear resistance: 20000 cycles Electrical wear resistance: 4000 cycles (at 400 V) Protection level (front panel): IP20 Operating temperature: from -25 to +70 °C Care temperature: from -40 to +80 °C Compliance with standards: IEC/EN 60947-2 Height: 255 mm Width: 140 mm Depth: 157 mm Weight: 5.5 kg