Number of poles: 3
Nominal flow (In): 63 A
Connection characteristic: C
Nominal limiting voltage (Icu) at 400 V AC: 25 kA
Rated operating voltage (Ics) at 400 V AC: 25 kA
Sputter type: Thermomagnetic
Type of vimicach: Co...
Number of poles: 3
Nominal flow (In): 63 A
Connection characteristic: C
Nominal limiting voltage (Icu) at 400 V AC: 25 kA
Rated operating voltage (Ics) at 400 V AC: 25 kA
Sputter type: Thermomagnetic
Type of vimicach: Compact automatic vimicach
Series: AZ-3
Externally assigned to the virobu: AZ-3-C63
Nominal operating voltage (Ue): 230/400 V AC
Nominal insulation voltage (Ui): 690 V
Nominal impulse voltage (Uimp): 6 kV
Frequency: 50/60 Hz
Strum type: Zmіnny (AC)
Mitigation flow range (C-characteristic): 5-10 x In (315-630 A)
Housing protection level: IP40
Terminal protection level: IP20
Maximum span of the connected cable (flexible): 50 mm²
Maximum retin Connectable cable (hard): 70 mm²
Terminal tightening torque: 4 Nm
Operating temperature: -25 ... +70 °C
Storage temperature: -40 ... +85 °C
Electrical wear resistance: 8,000 cycles
Mechanical wear resistance: 15,000 cycles
Mounting method: On a mounting plate / on screws
Compliance with standards: IEC/EN 60947-2
Overall height: 130 mm
Overall width: 75 mm
Overall depth: 70 mm
Weight: 0.6 kg
Reviews about Automatic circuit breaker 3p 63A AZ-3-C63 25kA EATON