Number of poles: 1
Nominal flow: 2 A
Connection characteristic: C
Borderline vimicious building: 6 kA
Nominal operating voltage of the exchanger: 230/400 V
Nominal insulation voltage: 500 V
Nominal impulse voltage: 4 kV
...
Number of poles: 1
Nominal flow: 2 A
Connection characteristic: C
Borderline vimicious building: 6 kA
Nominal operating voltage of the exchanger: 230/400 V
Nominal insulation voltage: 500 V
Nominal impulse voltage: 4 kV
Strum type: Zmіnny (AC)
Frequency: 50/60 Hz
Jet exchange class: 3
Width: 1 module (17.5 mm)
Height: 83 mm
Depth (from mounting rail): 70 mm
Electrical wear resistance: 20,000 cycles
Mechanical wear resistance: 20,000 cycles
Mounting type: DIN rail (EN 60715)
Maximum span of the connected wire conductor: 16 mm²
Maximum span of the connected hard conductor: 25 mm²
Terminal tightening torque: 2.8 Nm
Protection level (clem): IP20
Step zakhistu (front panel after installation): IP40
Operating temperature range: -25...+70 °C
Temperature range: -25...+80 °C
Overvoltage category: III
Congestion step: 2
Maximum height above the sea level: 2000 m
Power supply per pole: 0.7 W
Compliance with standards: EN 60898-1
Indication of contact position: Yes (green/red)
Zakhist vid vipadkovogo dotik: So
Housing material: Self-extinguishing thermoplastic
Weight: 0.125 kg