Type of attachment: Automatic vimicach power compact
Virobnik: Hager
Series: x160
Model/Article: HNA063H
Nominal flow (In): 63 A
Number of poles: 3
Rated operating voltage (Ue): 400/415V AC
Nominal insulation voltage (Ui...
Type of attachment: Automatic vimicach power compact
Virobnik: Hager
Series: x160
Model/Article: HNA063H
Nominal flow (In): 63 A
Number of poles: 3
Rated operating voltage (Ue): 400/415V AC
Nominal insulation voltage (Ui): 690V
Nominal impulse voltage (Uimp): 8 kV
Nominal short circuit limit commutation value (Icu) at 400/415V AC: 40 kA
Rated operating switching short circuit capacity (Ics) at 400/415V AC: 40 kA
Wiki category: A
Sputter type: Thermomagnetic
Adjustment of thermal sprayer (Ir): Regulated
Thermal blower regulation range: 50.4 - 63 A (0.8 - 1 x In)
Adjustment of magnetic spitter (Ii): Fixed
Magnetic sprayer application value (Ii): 630 A (10 x In)
Installation method: Stationary
Connection type: Front panel, screw terminals
Maximum overcut of the connected conductor: 70 mm²
Protection level: IP20
Operating temperature range: -25°C to +70°C
Compliance with standard: IEC/EN 60947-2
Mechanical wear resistance: 20,000 cycles
Electrical wear resistance: 10,000 cycles
Height: 165 mm
Width: 75 mm
Glibina: 86 mm